-
- -
- -
2006 International Plumbing Code (IPC)
Section 202 - General Definitions
AIR ADMITTANCE VALVE
One-way valve design to allow air to enter the plumbing drainage
system when negative pressures develop in the piping system.
The device shall close by gravity and seal the vent terminal
at zero differential pressure (no flow conditions) and under
positive internal pressures. The purpose of an air admittance
valve is to provide a method of allowing air to enter the
plumbing drainage system without the use of a vent extended
to open air and to prevent sewer gases from escaping into
a building.
Section 303 - Materials
PLASTIC PIPE, FITTINGS, AND COMPONENTS
All plastic pipe, fittings and components shall be third-party
certified as conforming to NSF 14.
Section 905 - Vent Connections
905.1 - Connection
All individual, branch and circuit vents shall connect to
a vent stack, stack vent, air admittance valve or extend to
the open air.
Section 917 - Air Admittance Valves
917.1 General
Vent systems utilizing air admittance valves shall comply
with this section. Individual-and-branch-type air admittance
valves shall conform to ASSE 1051.
917.2 Installation
The valves shall be installed in accordance with the requirements
of this section and the manufacturer's installation instructions.
Air admittance valves shall be installed after the DWV testing
required by Section 312.2 or 312.3 has been performed.
917.3
Where permitted. Individual, branch and circuit vents shall
be permitted to terminate with a connection to an air admittance
valve. The air admittance valve shall only vent fixtures that
are on the same floor level and connect to a horizontal branch
drain. The horizontal branch drain shall conform to Section
917.3 or Section 917.3.2.
917.3. 1
Location of branch. The horizontal branch drain shall connect
to the drainage stack or building drain a maximum of four
branch intervals from the top of the stack.
917.3.2
Relief vent. The horizontal branch shall be provided with
a relief vent that shall connect to a vent stack, or stack
vent, or extend outdoors to the open air. The relief vent
shall connect to the horizontal branch drain between the stack
air building drain and the most downstream fixture drain connected
to the horizontal branch drain. The relief vent shall be sized
in accordance with Section 916.2 and installed in accordance
with Section 905. The relief vent shall be permitted to serve
as the vent for other fixtures.
917.4
Location The air admittance valve shall be located a minimum
of 4 inches 9102 mm) above the horizontal branch drain or
fixture drain being vented. The air admittance valve shall
be located within the maximum developed length permitted for
the vent. The air admittance valve shall be installed a minimum
of 6 inches (152 mm) above insulation materials.
917.5
Access and Ventilation Access shall be provided to all air
admittance valves. The valve shall be located within a ventilated
space that allows air to enter the valve.
917.6 - Size
The air admittance valve shall be rated in accordance with
the standard for the size of the vent to which the valve is
connected.
917.7 - Vent required
Within each plumbing system, a minimum of one stack vent or
vent stack shall extend outdoors to the open air.
917.8 - Prohibited Installations
Air admittance valves shall not be installed in non neutralized
special waste systems as descried in Chapter 8. Valves shall
not be located in spaces utilized as supply or return air
plenums.
“Portions of this web site / publication reproduce
sections from the 2006 International Residential Code
for One and Two Family Dwellings and from the 2006
International Plumbing Code, International Code Council,
Inc., Falls Church, Virginia. Reproduced with permission.
All Rights reserved.”
Back to top
2006 INTERNATIONAL RESIDENTIAL CODE (IRC)
Section P3114 - Air Admittance Valves
P3114.1 General.
Vent systems utilizing air admittance valves shall comply
with this section. Individual-and-branch-type air admittance
valves shall conform to ASSE 1051. Stack type air admittance
valves shall conform to ASSE 1050.
3114.2 Installation.
The valves shall be installed in accordance with the requirements
of this section and the manufacturer's installation instructions.
Air admittance valves shall be installed after the DWV testing
required by Section P2503.5.1 or P 2503.5.2 has been performed.
3114.3 Where permitted.
Individual vents, branch vents, circuit vents and stack vents
shall be permitted to terminate with a connection to an air
admittance valve.
3114.4 Location
Individual and branch air admittance valves shall be located
a minimum of 4 inches (102 mm) above the horizontal branch
drain or fixture drain being vented. Stack-type air admittance
valves shall be located a minimum of 6 inches (152 mm) above
the flood level rim of the highest fixture being vented. The
air admittance valve shall be located within the maximum developed
length permitted for the vent. The air admittance valve shall
be installed a minimum of 6 inches (152 mm) above insulation
materials installed in attics.
3114.5 Access and Ventilation
Access shall be provided to all air admittance valves. The
valve shall be located within a ventilated space that allows
air to enter the valve.
3114.6 Size
The air admittance valve shall be rated in accordance with
the standard for the size of the vent to which the valve is
connected.
3114.7 Vent required.
Within each plumbing system, a minimum of one stack vent or
vent stack shall extend outdoors to the open air.
"Portions of this web site / publication reproduce sections
from the 2006 International Residential Code for One and
Two Family Dwellings and from the 2006 International
Plumbing Code, International Code Council, Inc., Falls
Church, Virginia. Reproduced with permission. All Rights reserved."
Back to top.
2006 UNIFORM PLUMBING CODE (UPC)
Chapter 3 - General Regulations
301.2 Alternate Materials and Methods of Construction
Equivalency
Nothing in this code is intended to prevent the use of systems,
methods, or devices of equivalent or superior quality, strength,
fire resistance, effectiveness, durability, and safety over
those prescribed by this code. Technical documentation shall
be submitted to the Authority Having Jurisdiction to demonstrate
equivalency. The Authority Having Jurisdiction shall approve
the system method or device when determined to be equivalent
or superior.
However, the exercise of this discretionary approval by the
Authority Having Jurisdiction shall have no effect beyond
the jurisdictional boundaries of said Authority Having Jurisdiction.
Any alternate material or method of construction so approved
shall not be considered as conforming to the requirements
and/or intent of this code for any purpose other than that
granted by the Authority Having Jurisdiction when the submitted
date does not prove equivalency.
301.2.1 Testing
The Authority Having Jurisdiction shall have the authority
to require tests, as proof of equivalency.
301.2.1.1
Tests shall be made in accordance with approved standards,
by an approved testing agency at the expense of the applicant.
In the absence of such standards, the Authority Having Jurisdiction
shall have the authority specify the test procedure.
301.2.1.2
The Authority Having Jurisdiction shall have the authority
to require tests to be made or repeated if, at any time, there
is reason to believe that any material or device no longer
conforms to the requirements on which its approval was based.
Back to top
2006 NATIONAL STANDARD PLUMBING CODE (NSPC)
Appendix E - Special Design Plumbing Systems
NOTE: Following sections of the code
cover the special design requirements that apply to all of
the systems in Appendix E.
E.1 GENERAL REQUIREMENTS
E.1.1
Special design plumbing systems shall include all systems
that vary in detail from the requirements of this Code.
E.1.2
The provisions of this Appendix shall control the design,
installation, and inspection of special design plumbing systems.
E.1.3
Special design plumbing systems shall conform to the Basic
Principles of this Code.
E.1.4
Special design plumbing systems shall be designed by a registered
design professional who is licensed to practice in the particular
jurisdiction.
E.2 Plans, Specifications, and Computations
E.2.1
Plans, specifications, computations, and other related data
for special design plumbing systems, prepared by the registered
design professional, shall be submitted to the Authority Having
Jurisdiction for review and approval prior to installation.
E.2.2
The design plans shall indicate that the plumbing system (or
portions thereof) is a special design system.
E.3 Installation of Special Design Plumbing Systems
E.3.1
Special design plumbing systems shall be installed according
to established, tested and approved criteria, including manufacturer’s
instructions.
E.3.2
The installation shall comply with Chapter 2 – General
Regulations and other applicable requirements of this Code.
E.4 Certification of Compliance
E.4.1
Inspection shall be made by the Authority Having Jurisdiction
to ensure conformance with data submitted for approval and
the applicable requirements of this Code.
E.4.2
The complete installation and performance of the special design
plumbing system shall be certified by the registered design
professional as complying with the requirements of the special
design.
E.8 Air Admittance Valves
E.8.1 - Definition
Air admittance valve: A one way valve designed to allow air
to enter the plumbing drainage system when negative pressures
develop in the system. The device closes by gravity, without
springs or other mechanical means, and seals the vent terminal
at zero differential pressure (no flow conditions) and also
under positive internal pressure. The purpose of an air admittance
valve are (1) to provide a method of allowing air to enter
the plumbing drainage system without the need for a vent extended
outdoors to open air, and (2) to prevent sewer gases from
escaping into the building.
E.8.2 - Where permitted
E.8.2.1
Branch, circuit, common, continuous and individual vents shall
be permitted to terminate with a connection to an individual
or branch type air admittance valve complying with ASSE 1051.
Individual and branch type air admittance valves shall only
vent fixtures that are on the same floor level and connect
to a horizontal branch drain.
E.8.2.2
Vent stacks and stack vents shall be permitted to terminate
at a stack type air admittance valve complying with ASSE 1051.
EXCEPTIONS:
(1.) Vent stacks and stack vents serving
drainage stacks that exceed six (6) branch intervals in height.
(2.) Vent stacks and stack vents that serve
relief vents in Section E.8.3
E.8.2.3
Air admittance valves shall not be permitted in the following
applications:
a. vents for special waste drainage systems
(Sections 9.4.1 and 9.4.2)
b. vents for sewage pump ejector pump sites
c. vents for pneumatic sewage ejectors
d. suds pressure zone venting e. relief vents
required by Section E.8.3.1
E.8.3 - Relief Vents
E.8.3.1
A relief vent shall be provided where a horizontal branch
drain that is vented by one or more air admittance valves
connects to a drainage stack more than four (4) branch intervals
from the top of the stack. The relief vent shall connect vertically
to the horizontal branch drain between the drainage stack
and the most downstream fixture drain connection on the horizontal
branch drain. Relief vents shall extend from the horizontal
branch drain to a vent stack, or other vent that terminates
outdoors in open air.
E.8.3.2
Relief vents shall be the full size of the horizontal branch
drain that they serve, up to a 3" maximum required size.
E.8.4 - Installation
E.8.4.1
Air admittance valves shall be installed in accordance with
the manufacturer's instructions and Section E.8.
E.8.4.2
Air admittance valves shall connect to fixture trap arms within
the maximum allowable trap arm lengths in Table 12.8.1.
E.8.4.3
Individual and branch type air admittance valves shall be
installed at least 4 inches above the top of the trap arm
or horizontal branch drain that they serve.
E.8.4.4
Stack type air admittance valves shall be installed at least
6 inches above the flood level rim of the highest fixture
served by the valve.
E.8.4.5
Air admittance valves shall be installed in accessible locations
having free movement of air to enter the valve.
E.8.4.6
Air admittance valves shall not be installed in HVAC supply
or return air plenums or other areas subject to other than
atmospheric conditions.
E.8.4.7
Air admittance valves installed in insulated attic or ceiling
spaces shall be installed in free air at least 6 inches above
the insulation.
E.8.4.8
Air admittance valves shall be the same size as the vent pipe
to which they are connected.
E.8.4.9
Air admittance valves shall not be installed until all required
leak tests of the drainage and vent piping are successfully
completed.
E.8.5 - Vent to outdoors required
In each plumbing drainage system vented by one or more air
admittance valves, at least one vent shall extend outdoors
to open air.
E.8.6 - Referenced Standards
E.8.6.1 ASSE 1050-2002 Stack Air Admittance Valves for Sanitary
Drainage Systems
E.8.6.2 ASSE 1051-2002 Individual and Branch Type Air Admittance
Valves for Plumbing Drainage Systems.
NOTE: The provisions are from the 2005 Supplement to the 2003 NSPC and from the 2006 NSPC.
Back to top
2005 NATIONAL PLUMBING CODE OF CANADA
Division A
1.4.1.2 Definition
Air Admittance valve means a one-way valve designed
to allow air to enter the drainage system when the
pressure in the plumbing system is less than the
atmospheric pressure.
(See Appendix Note A-2.2.10.16.(1) of Division B.)
Division B
2.2.10.16 Air Admittance Valves
1) Air admittance valves shall conform to ASSE 1051,
“Individual and Branch Type Air Admittance Valves for
Sanitary Drainage Systems.” (See Appendix A.)
2.5.9 Air Admittance Valves
(See A-2.2.10.16.(1) in Appendix A.)
2.5.9.1 Air Admittance Valve as a Vent Terminal
1) Individual vents may terminate with a connection
to an air admittance valve as provided in Articles
2.5.9.2 and 2.5.9.3. (See also Sentence 2.2.10.16.(1).)
2.5.9.2 Air Admittance Valves
1) Air admittance valves shall only be used to vent
a) fixtures located in island counters,
b) fixtures that may be affected by frost closure
of the vent due to local climatic conditions,
c) fixtures in one-and two-family dwellings undergoing
renovation, or
d) installations where connection to a vent may not be practical.
2) Air admittance valves shall be located
a) not less than 100 mm above the horizontal branch
drain or fixture drain being vented,
b) within the maximum developed length permitted
for the vent, and
c) not less than 150 mm above insulation materials.
2.5.9.3 Installation Conditions
1) Air admittance valves shall not be installed in
supply or return air plenums, or in locations where they may
be exposed to freezing temperatures.
2) Air admittance valves shall be installed in accordance
with the manufacturer’s installation instructions.
3) Air admittance valves shall be rated for the size
of vent pipe to which they are connected.
4) Installed air admittance valves shall be
a) accessible, and
b) located in a space that allows for air to enter the valve
5) Every drainage system shall have one vent that
terminates to the outdoors in conformance with Sentence 2.5.6.2.(1).
Back to top
|